Levelflex FMP53 FOUNDATION Fieldbus Commissioning (block-based operation)
Endress+Hauser 41
11.4 Configuration of a level measurement
The Setup method can also be used to configure the measurement. It is called up via the
SETUP (TRDSUP) transducer block.
A0011360
12 Configuration parameters for level measurements in liquids
LN = Length of probe R = Reference point of the measurement
D = Distance E = Empty calibration (= Zero point)
L = Level F = Full calibration (= span)
If for rope probes the DC value is less than 7, then measurement is not possible in the
area of the straining weight. In these cases, the maximum allowed value for the empty
calibration E is LN - 250 mm (LN - 10 in).