Commissioning (block-based operation) Levelflex FMP53 FOUNDATION Fieldbus
42 Endress+Hauser
Step Block Parameter Action
1 SETUP (TRDSUP) Distance unit
(distance_unit)
Select distance unit.
Selection:
• 1010: m
• 1013: mm
• 1018: in
• 1019: ft
2 SETUP (TRDSUP) Tank type (tank_type) Select tank type.
Selection:
• 32816: Bypass / pipe
• 33288: Metallic
• 33302: Coaxial
• 33432: Twin rope
• 33433: Twin rod
• 33437: Rope centering disc metallic
• 33438: Rod centering disc metallic
• 33441: Non metallic
• 33444: Mounted outside
3 SETUP (TRDSUP) Tube diameter
(tube_diameter)
1)
Enter the diameter of the bypass or stilling well.
4 SETUP (TRDSUP) Medium group
(medium_group)
Select medium group.
Selection:
• 316: water based (DC>4)
• 256: other (DC≥ 1.9)
2)
5 SETUP (TRDSUP) Empty calibration
(empty_calibration)
Enter the distance E between the reference point R
and the minimum level (0%).
6 SETUP (TRDSUP) Full calibration
(full_calibration)
Enter distance F between the minimum (0%) and
maximum (100%) level.
7 SETUP (TRDSUP) Level (level) Displays the measured level L.
8 SETUP (TRDSUP) Distance
(filtered_dist_val)
Displays the distance D between the reference
point R and the level L.