Levelflex FMP53 FOUNDATION Fieldbus Commissioning (block-based operation)
Endress+Hauser 43
Step Block Parameter Action
9 SETUP (TRDSUP) Signal quality
(signal_quality)
Displays the signal quality of the level echo.
10 SETUP (TRDSUP) Confirm distance
(confirm_distance)
Compare the displayed distance to the real distance
in order to start the recording of the mapping
curve.
Selection:
• 179: Manual map
• 32847: Delete all
• 32859: Distance ok
• 32860: Distance too big
• 32861: Distance too small
• 32862: Distance unknown
• 33100: Tank empty
1) only available for coated probes and "Tank type" = "Bypass/pipe"
2) If required, lower DCs can ben entered into the "DC value (dc_value)" parameter. However, for DC<1.6 the
measuring range may be reduced; for details please contact Endress+Hauser.
11.5 Configuration of the on-site display
11.5.1 Factory settings of the on-site display for level measurements
Parameter Factory setting for devices with 1 current
output
Factory setting for devices with 2 current
outputs
Format display 1 value, max. size 1 value, max. size
Value 1 display Levele linearized Levele linearized
Value 2 display Distance Distance
Value 3 display Current output 1 Current output 1
Value 4 display None Current output 21
The on-site display can be adjusted in the DISPLAY (TRDDISP) transducer block.
11.6 Configuration management
After commissioning, you can save the current device configuration, copy it to another
measuring point or restore the previous device configuration. You can do so using the
Configuration management parameter and its options.
Navigation path in the operating menu
Setup → Advanced setup → Conf.backup disp → Config. managem.
Block operation
Block: DISPLAY (TRDDISP)
Parameter: Configuration management (configuration_management)