Commissioning (via operating menu) Levelflex FMP53 FOUNDATION Fieldbus
36 Endress+Hauser
10.5 Configuration of a level measurement
F
L
D
E
20 mA
100%
4 mA
0%
LN
R
A0011360
 10 Configuration parameters for level measurements in liquids
LN = Length of probe R = Reference point of the measurement
D = Distance E = Empty calibration (= Zero point)
L = Level F = Full calibration (= span)
1. Setup → Device tag
Enter tag for measuring point.
2. Setup → Distance unit
Select distance unit.
3. Setup → Tank type
Select tank type.
4. Setup → Tube diameter (only if "Tank type" = "Bypass / pipe")
Enter the diameter of the bypass or stilling well.
5. Setup → Medium group
Select medium group (Others or Water based (DC >= 4))
6. Setup → Empty calibration
Enter the distance E between the reference point R and the minimum level (0%).
7. Setup → Full calibration
Enter distance F between the minimum (0%) and maximum (100%) level.