Levelflex FMP53 FOUNDATION Fieldbus Commissioning (block-based operation)
Endress+Hauser 45
11.7 Configuration of the event behavior according to the FOUNDA-
TION Fieldbus specification FF912
The device complies with the FOUNDATION Fieldbus specification FF912. This has - among
other things - the following consequences:
The diagnsotic category according to NAMUR recommendation NE107 is transmitted via
the fieldbus in a manufacturer-independent form:
F: Failure
C: Function check
S: Out of specification
M: Maintenance required
The diagnostic category of pre-defined groups of events can be adjusted by the user
according to the requirements of the specific application.
Certain events can be separated from their group and can be handled individually:
941: Echo lost
942: In safety distance
Additional information and remedial measures are transmitted together with the event
message via the fieldbus.
The diagnostic messages according to FF912 are available in the host only if the Multi-
bit support option has been activated in the FEATURE_SEL parameter of the Resource
block. For reasons of compatibility, this option is not activated on delivery: