Levelflex FMP53 FOUNDATION Fieldbus Commissioning (block-based operation)
Endress+Hauser 47
Severity of the event Default diagnostic category Source of the
event
Bit Events within the group
Configuration 25 • C411: Up-/download
• C431: Trim
• C484: Simulation failure
mode
• C485: Simulation measured
value
• C491: Simulation current
output
• C585: Simulation distance
Process 24 not used in Levelflex
Severity of the event Default diagnostic category Source of the
event
Bit Events within the group
Low severity Out of specification (S) Sensor 23 not used in Levelflex
Electronics 22 not used in Levelflex
Configuration 21 S441: Current output 1
Process 20 • S801: Energy too low
• S825: Operating temperature
• S921: Change of reference
• S942: In safety distance
1)
• S943: In blocking distance
• S944: Level range
• S968: Level limited
1) This event can be removed from the group in order to define its behavior individually; see section "Configurable
area".
Severity of the event Default diagnostic category Source of the
event
Bit Events within the group
Lowest severity Maintenance required (M) Sensor 19 not used in Levelflex
Elektronics 18 • M270: Main electronics
failure
• M272: Main electronics
failure
• M311: Electronics failure
Configuration 17 M438: Data set
Process 16 M803: Current loop 1