Levelflex FMP53 FOUNDATION Fieldbus Commissioning (block-based operation)
Endress+Hauser 47
Severity of the event Default diagnostic category Source of the
event
Bit Events within the group
Configuration 25 C411: Up-/download
C431: Trim
C484: Simulation failure
mode
C485: Simulation measured
value
C491: Simulation current
output
C585: Simulation distance
Process 24 not used in Levelflex
Severity of the event Default diagnostic category Source of the
event
Bit Events within the group
Low severity Out of specification (S) Sensor 23 not used in Levelflex
Electronics 22 not used in Levelflex
Configuration 21 S441: Current output 1
Process 20 S801: Energy too low
S825: Operating temperature
S921: Change of reference
S942: In safety distance
1)
S943: In blocking distance
S944: Level range
S968: Level limited
1) This event can be removed from the group in order to define its behavior individually; see section "Configurable
area".
Severity of the event Default diagnostic category Source of the
event
Bit Events within the group
Lowest severity Maintenance required (M) Sensor 19 not used in Levelflex
Elektronics 18 M270: Main electronics
failure
M272: Main electronics
failure
M311: Electronics failure
Configuration 17 M438: Data set
Process 16 M803: Current loop 1