Levelflex M FMP40
20 Endress+Hauser
Performance characteristics
Reference operating
conditions
Temperature = +20 °C ±5 °C
Pressure = 1013 mbar abs. ±20 mbar
Humidity = 65 % ±20 %
Reflection factor 0.8 (surface of the water for coax probe, metal plate for rod and rope probe with min.
1m)
Flange for rod or rope probe 30 cm
Distance to obstructions 1m
For interface measurement:
Coax probe
DC of the lower medium = 80 (water)
DC of the upper medium = 2 (oil)
Maximum measured error Typical data under reference operating conditions: DIN EN 61298-2, percentage values in relation to the span.
If the reference conditions are not met, the offset/zero point arising from the mounting situation may be up to
±12 mm for rope and rod probes. This additional offset/zero point can be compensated for by entering a
correction (function "Offset" (057)) during commissioning.
Differing from this, the following measuring error is present in the vicinity of the level
(electronic version level and interface measurement):
If for rope probes the DC value is less than 7, then measurement is not possible in the area of the straining
weight (0 to 250 mm from end of probe; lower blocking distance).
Output: Digital Analog
Sum of non-linearity,
non-repeatability and
hysteresis
Level (electronic version level and interface measurement):
Measuring range up to 10 m: ±3 mm
Measuring range >10 m: ±0.03 %
For PA-coated rope probes:
Measuring range up to 5 m: ±5 mm
Measuring range > 5 m: ±0.1 %
±0.06 %
Interface (only for electronic version "K" interface measurement):
Measuring range up to 10 m: ±10 mm
If the thickness of the interface is < 60 mm, the interface can no longer
be differentiated from the overall level such that both output signals are
identical.
Offset / Zero ±4 mm ±0.03 %
L00-FMP4xxxx-05-00-00-en-001 L00-FMP4xxxx-05-00-00-en-002
rod probe and coax probe
-80
-60
-40
-20
0
20
40
60
80
0 50 100 150 200 250 300
distance from probe end [mm]
sum of non-linearity, non-repeatability
and hysteresis [mm]
DC = 2
DC > 7
rope probe
-80
-60
-40
-20
0
20
40
60
80
0 50 100 150 200 250 300
distance from probe end [mm]
sum of non-linearity, non-repeatability
and hysteresis [mm]
DC > 7