Levelflex M FMP40
Endress+Hauser 37
Installation at an angle
Installation for difficult-to-
access process connections
For tight spaces or temperatures above that in the graphic ( ä 40), the electronics housing can be ordered
with distance pipe or connecting cable (separate housing).
For mechanical reasons, the probe should be
installed as vertically as possible.
With inclined installations the probe length has to
be adjusted in dependence to the installation angle.
up to 1 m = 30°
up to 2 m = 10°
up to 4 m = 5°.
L00-FMP4xxxx-17-00-00-en-048
rope probe
mounting angle
Installation with spacer tube
When mounting please observe engineering hints
( ä 22) the following points:
After mounting, the housing can be turned 350° in
order to make it easier to access the display and the
connection compartment.
The max. measuring range is reduced to 34 m.
L00-FMP4xxxx-17-00-00-en-014
400
Ø 60,3
Ø 76