Levelflex M FMP40
36 Endress+Hauser
Installation in nozzle DN300
Installation
with heat insulation
If process temperatures are high, FMP40 must be included in normal tank insulation to prevent the
electronics heating up as a result of heat radiation or convection.
The insulation may not exceed beyond the points labeled "MAX" in the drawings.
If installation in 300 mm (12") nozzles is
unavoidable, installation must be carried out in
accordance with the sketch on the right.
L00-FMP4xxxx-17-00-00-en-034
280
> 350
DN300
> DN400
pipe
150…180ø
plate diameternozzle diameter
plate
Approx. flush with
the lower edge of
the nozzle 50 mm).
lower edge of
the nozzle
Process connection with adapter
G¾, G1½, ¾NPT or 1½NPT
Process connection with flange DN40 to DN200
L00-FMP40xxx-17-00-00-en-003
L00-FMP40xxx-17-00-00-en-002
MAX
max. 150° C (302° F)
tank insulation
MAX
40
max. 150° C (302° F)
tank insulation