Levelflex M FMP40 FOUNDATION Fieldbus Wiring
Endress+Hauser 21
Current consumption
The following values are the voltages across the terminals directly at the device:
Current consumption
Overvoltage protection
If the measuring device is used for the level measurement in flammable liquids which requires
the use of an overvoltage protection according to EN/IEC 60079-14 or EN/IEC 60060-1
(10 kA, Puls 8/20 μs) it has to be ensured that
the measuring device with integrated overvoltage protection with gas discharge tubes within
the T12-enclosure is used, refer to product overview in the Operating instructions on CD-ROM
or
this protection is achieved by the use of other appropriate measures (external protection
devices e.g. HAW562Z).
3.7 Screening/potential matching
You achieve optimum screening against disturbances if the screening is connected on both
sides (in the cabinet and on the device). If you have to reckon with potential equalisation
currents in the plant, only earth screening on one side, preferably at the transmitter.
When using in hazardous areas, you must observe the applicable regulations and the separate
Ex documentation.
Type Terminal voltage
standard 9 V to 32 V
Supply voltage 9 V to 32 V
1)
1) There may be additional restrictions for devices with an explosion protection certificate. Refer to the notes in the
appropriate Safety Instructions (XA).
Lift-off voltage 9 V
Nominal current 15 mA
Starting current 15 mA
Error current 0 mA
FISCO/FNICO conformal Compliant
Polarity sensitive No