Commissioning Levelflex M FMP40 FOUNDATION Fieldbus
34 Endress+Hauser
5.4.7 Function "probe length" (031)
Use this function to select whether the probe length was changed after factory calibration. Only
then is it necessary to enter or correct the probe length.
Selection:
not modified
modified
!
Note!
If "modified" was selected in the "probe length" (031) " function, the probe length is defined
in the next step.
5.4.8 Function "probe" (032)
Use this function to select whether the probe is at the time of the commisioning uncovered or
covered.If the probe is uncovered, the Levelflex can determine the probe length automatically
"determine length" (034) function. If the probe is covered, a correct entry is required in the
"probe length" (033) function.
Selection:
free
covered
5.4.9 Function "probe length" (033)
Use this function, the probe length can be entered manually.