Levelflex M FMP40 FOUNDATION Fieldbus Commissioning
Endress+Hauser 41
Maximum measured error
Typical statements for reference conditions:
DIN EN 61298-2, percentage of the span.
If the reference conditions are not met, the offset/zero arising from the mounting situation may
be up to ±12 mm. This additional offset/zero can be compensated for by entering a correction
(function "offset" (057))during commissioning.
Differing from this , the following measuring error is present in the vicinity of the probe end:
!
Note!
Please reenter the blocking distance in the function group "extended calibr." (05) funktion
"upper block dist." (059) when installing the device in a high nozzle:
upper blocking distance (UB) = nozzle height (H) + 50 mm.
Output: digital analog
sum of non-linearity,
non-repeatabilityand hysteresis
measurig range:
up to 10 m: ±3 mm
> 10 m: ± 0.03 %
for PA coated rope
measuring range:
–up to 5 m: ±5mm
> 5 m: ± 0.1 %
± 0.06 %
Offset / Zero ±4 mm ± 0.03 %
L00-FMP4xxxx-05-00-00-en-001 L00-FMP4xxxx-05-00-00-en-002
rod probe and coax probe
-80
-60
-40
-20
0
20
40
60
80
0 50 100 150 200 250 300
distance from probe end [mm]
sum of non-linearity, non-repeatability
and hysteresis [mm]
DC = 2
DC > 7
rope probe
-80
-60
-40
-20
0
20
40
60
80
0 50 100 150 200 250 300
distance from probe end [mm]
sum of non-linearity, non-repeatability
and hysteresis [mm]
DC > 7