Liquiphant M FTL51C
10 Endress+Hauser
Electronic insert FEL55 (8/16 mA)
Power supply Supply voltage: DC 11 to 36 V
Power consumption: < 600 mW
Reverse polarity protection
Overvoltage protection FEL55: overvoltage category III
Electrical connection Two-wire connection for separate switching unit
Output signal
Signal on alarm Output signal on power failure or in the event of damaged sensor: < 3.6 mA
Connectable load • R = (U - 11 V) : 16.8 mA
• U = connection voltage: DC 11 to 36 V (in wet environments DC 11 to 35 V)
Example: PLC with 250 with 2-wire version
250 = (U – 11V) / 16.8 mA
4.2 [/] = U – 11 V
U = 15.2 V
For separate switching unit.
Signal transmission 16/8 mA on two-wire cabling.
For connection to programmable logic controllers
(PLC) for example, AI modules 4 to 20 mA to
EN 61131-2.
Output signal jump from high to low current on
point level.
Fuse required for non-Ex applications!
Only use power units with safe galvanic isolation (e.g.
SELV).
L00-FTL5xxxx-04-05-xx-en-000