EasyManua.ls Logo

Endress+Hauser Liquiphant M FTL51C - Electronic Insert FEL50 A (PROFIBUS PA); Power Supply; Electrical Connection

Endress+Hauser Liquiphant M FTL51C
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Liquiphant M FTL51C
Endress+Hauser 15
Electronic insert FEL50A (PROFIBUS PA)
Power supply Bus voltage: DC 9 to 32 V
Bus current:
12.5 mA +/– 1.0 mA (software version: 01.03.00, hardware version: 02.00)
10.5 mA +/– 1.0 mA (software version: 01.03.00, hardware version: 01.00)
Electrical connection Two-wire connection for power supply and data transfer
L00-FTL5xxxx-04-05-xx-xx-100
For connecting to PROFIBUS PA
Additional functions:
Digital communication enables the
representation, reading and editing
of the following parameters:
Fork frequency, switch-on frequency,
switch-off frequency, switch-on time and
switch-off time, status, measured value, density
change
Matrix locking possible
Switch to WHG mode possible
(WHG approval)
For a detailed description, see BA00198F
L00-FTL5xxxx-04-05-xx-en-005
PA PA+
PROFIBUS PA
E
X
E
X
U– 9…32 V DC
...
12
FEL50A
Segment coupler
PLC
PROFIBUS DP
PROFIBUS PA
E
X
E
X
PC
Proficard Profiboard/
Segment plercou

Table of Contents

Other manuals for Endress+Hauser Liquiphant M FTL51C

Related product manuals