Liquiphant M FTL51C
20 Endress+Hauser
When fork is exposed: 1.0 s
Available on request: 0.2 s; 1.5 s or 5 s (when the tuning fork is covered or exposed)
Operating conditions
Installation instructions
!
Note!
The switch points of the LiquiphantM are at other positions to those of the previous version
LiquiphantII.
Minimum distance between the tip of the fork and the tank wall or pipe wall: 10 mm
Synthetic coating:
L00-FTL5xxxx-06-05-xx-xx-051
Mounting from above Mounting from below Mounting from the side
Enamel coating:
L00-FTL5xxxx-06-05-xx-xx-051
Mounting from above Mounting from below Mounting from the side
Examples of mounting Examples of mounting with regard to the viscosity of the liquid and the tendency to form buildup
Optimum mounting, without problem even with high viscosity:
L00-FTL51Cxx-11-05-xx-xx-002
Vertical from above Flush-mounted from the side
Switch points on the sensor depend on the mounting position, with reference to water,
Density 1 g/cm

(SGU), 23 °C (73 °F), p
e
0 bar (0 psi).
13
(0.51)
4
(0.16)
4
( 0.16)
mm (in)
10
(0. )39
40
(. )1 57
13
(0.51)
4
( 0.16)
mm (in)
10
(0. )39
46.5
(. )1 83
8
(0. 1)3