Liquiphant M FTL51C
6 Endress+Hauser
Electronic insert FEL51 (AC 2-wire)
Power supply Supply voltage: AC 19 to 253 V
Power consumption: < 0.83 W
Residual current consumption: < 3.8 mA
Short-circuit protection
Overvoltage protection FEL51: overvoltage category III
Electrical connection Two-wire AC connection
Output signal
Signal on alarm Output signal on power failure or in the event of damaged sensor: < 3.8 mA
Connectable load Voltage drop via FEL51
12 V
Residual current if electrical switch is blocked: 3.8 mA
Load switched directly into the power supply circuit via the thyristor.
Transient (40 ms)
1.5 A, 375 VA at 253 V or 36 VA at 24 V (not short-circuit-proof)
The load is switched via an electronic switch directly in the power circuit.
Always connect in series with a load!
Not suitable for connection to low-voltage PLC inputs!
Switches the load directly into the power supply
circuit via an electronic switch.
Always connect in series with a load!
Check the following:
The residual current in blocked state
(up to 3.8 mA)
That for low voltage
the voltage drop across the load is such that
the minimum terminal voltage at the
electronic insert (19 V)
when blocked is not undershot.
the voltage drop across the electronics when
switched through is observed (up to 12 V)
That a relay cannot de-energize with holding
power below 3.8 mA.
If this is the case, a resistor should be
connected parallel to the relay. An RC module is
available under the part number: 71107226
When selecting the relay, pay attention to the
holding power / rated power (see "Connectable
load")
L00-FTL5xxxx-04-05-xx-en-007
L1
U~ max. 253 V AC
50/60 Hz
NNPE
(Ground)
1A
min.
19 V
12
FEL51
*
R
*
External load R
be connectedmust
Safety mode Level Output signal LEDs
green red
I
L
< 3.8 mA
L00-FTL2xxxx-07-05-
xx-xx-000
= load current
(switched through)
= residual current
(blocked)
= lit
= unlit
L00-FTL5xxxx-04-05-xx-xx-001
MAX
MIN