Micropilot FMR10 Diagnostics and troubleshooting
Endress+Hauser 27
Errors Possible cause Solution
Device cannot be operated via
SmartBlue
Password forgotten Contact the manufacturer's Service Department
Device cannot be operated via
SmartBlue
Sensor temperature too
high
If the ambient temperature results in an elevated
sensor temperature of >60 °C (140 °F), Bluetooth
communication may be disabled.
Shield the device, isolate it and cool it down if
necessary.
9.3 Diagnostic event in the operating tool
If a diagnostic event is present in the device, the status signal appears in the top left status
area of the operating tool along with the corresponding symbol for the event level in
accordance with NAMUR NE 107:
• Failure (F)
• Function check (C)
• Out of specification (S)
• Maintenance required (M)
Calling up remedial measures
‣
Navigate to the Diagnostics menu
In the Actual diagnostics parameter the diagnostic event is shown with event text