EasyManua.ls Logo

Endress+Hauser Micropilot FMR51 - Page 189

Endress+Hauser Micropilot FMR51
198 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Micropilot FMR51, FMR52 FOUNDATION Fieldbus Operating menu
Endress+Hauser 189
Description of parameters
Navigation  Expert → Diagnostics → Simulation
Assign measurement variable
Navigation  Expert → Diagnostics → Simulation → Assign meas.var.
Description Selct process variable to be simulated.
Selection Off
Level
Level linearized
Factory setting Off
Additional information The value of the variable to be simulated is defined in the Value process variable
parameter (→  189).
If Assign measurement variableOff, a simulation is active. This is indicated by a
diagnotic message of the Function check (C) category.
Value process variable
Navigation  Expert → Diagnostics → Simulation → Value proc. var.
Prerequisite Assign measurement variable (→  189)Off
Description Specify value of the process value being simulated.
User entry Signed floating-point number
Factory setting 0
Additional information Downstream measured value processing and the signal output use this simulation value. In
this way, users can verify whether the measuring device has been configured correctly.
Switch output simulation
Navigation  Expert → Diagnostics → Simulation → Switch sim.
Description Switch the simulation of the switch output on or off.
Selection Off
On
Factory setting Off

Table of Contents

Other manuals for Endress+Hauser Micropilot FMR51

Related product manuals