EasyManua.ls Logo

Endress+Hauser Nivector FTI26 - Short-Circuit Protection; Process; Process Temperature Range; Process Pressure Range

Endress+Hauser Nivector FTI26
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Nivector FTI26
12 Endress+Hauser
Short-circuit protection
Overload protection/short-circuit protection at I > 200 mA
IO-Link communication: 105 mA each if both switch outputs are active
Intelligent monitoring: Testing for overload at intervals of approx. 1.5 s; normal operation resumes
once the overload/short-circuit has been rectified.
Process
Process temperature range
–20 to +80 °C (–4 to +176 °F)
For Ex devices: –20 to +75 °C (–4 to +167 °F)
Process pressure range
–1 to +6 bar (–14.5 to +87 psi)
Process fluid
Powdery and fine-grained bulk solids
Grain size < 10 mm
Dielectric constant  1.3
Default values: ε
r
 > 1.6 with protector, ε
r
 > 2.0 without protector