Mounting Levelflex M FMP40 with PROFIBUS PA
24 Endress + Hauser
3.4.6 Special notes for bulk solids
Installation in concrete silos
Installation, for example, into a thick concrete ceiling should be made flush with the lower edge.
Alternatively, the probe can also be installed into a pipe that must not protrude over the lower edge
of the silo ceiling. The pipe should kept at a minimum length. Installation suggestions see diagram.
L00-FMP4xxxx-17-00-00-en-008
The centering disk should be used for tube diameter > 150 mm to prevent build-up in the inner
port of the tube.
In the case of bulk solids, as great a distance as
possible from the filling curtain is especially
important to avoid wear.
•In concrete silos, a large distance (B) should
be observed between the probe and the
concrete wall, if possible >= 1m, but at least
0.5m
The installation of rope probes must be carried
out carefully. If possible, installation should be
carried out when the silo is empty.
Check the probe regularly for defect.
L00-FMP4xxxx-17-00-00-xx-005
B
³ 100 mm ³ 100 mm
Ø 80...150 mm
metal
Extension rod /
Centering
(see accessories)
metal tube