Commissioning Levelflex M FMP40 with PROFIBUS PA
72 Endress + Hauser
L00-FMP4xxxx-14-00-06-en-008
Function "full calibr." (006)
This function is used to enter the distance from the minimum level to the maximum level (=span).
L00-FMP4xxxx-14-00-06-en-009
!
Note!
The usable measuring range lies between the lower and the upper blocking distance. The values for
empty distance (E) and span (F) can be set independently of this.
0%
E
E = empty calibration (= zero)
E
max
= probe length – lower blocking distance
⇒
ENDRESS + HAUSER
E
+
–
100%
0%
F
F = full calibration (= span)
F
max
= E – upper blocking distance