Levelflex M FMP40 with PROFIBUS PA Commissioning
Endress + Hauser 73
Display (008)
The distance measured from the reference point to the product surface and the meas. value
calculated with the aid of the empty adjustment are displayed. Check whether the values
correspond to the actual meas. value or the actual distance. The following cases can occur:
Distance correct – meas. value correct -> continue with the next function
"check distance" (051).
Distance correct – meas. value incorrect -> Check "empty calibr." (005)
Distance incorrect – meas. value incorrect -> continue with the next function
"check distance" (051).
Function "check distance" (051)
This function triggers the mapping of interference echoes. To do so, the measured distance must be
compared with the actual distance to the product surface. The following options are available for
selection:
Selection:
•distance = ok
dist. too small
dist. too big
dist. unknown
manual
probe free
L00-FMP4xxxx-14-00-06-en-010
distance = ok
Use this function at part-covered probe. Choosing function "manual" or "probe free" at free probe.
mapping is carried out up to the currently measured echo
The range to be suppressed is suggested in the "range of mapping" (052) function
ENDRESS + HAUSER
E
+
ENDRESS + HAUSER
E
+
+
+
distance too small distance = ok