Proline Promag 53 NEPSI Zone 1, Zone 21 0
Endress+Hauser 13
Terminal assignment of transmitter 53***-***********S
Terminal assignment of transmitter 53***-***********T
Transmitter
Terminal no. (inputs/outputs)
20 (+) 21 (–) 22 (+) 23 (–) 24 (+) 25 (–) 26 (+) 27 (–)
Assignment
Pulse/frequency output,
passive
Current output HART,
active
Electric circuit Ex ia Ex ia
Safety-related
values
––U
i
I
i
P
i
L
i
C
i
30 V DC
500 mA
600 mW
negligible
6 nF
U
o
I
o
P
o
L
o
IIC/IIB
C
o
IIC/IIB
1)
L
o
IIC/IIB
1)
C
o
IIC/IIB
U
i
I
i
P
i
L
i
C
i
21.8 V DC
90 mA
491 mW
4.1 mH/15 mH
160 nF/1160 nF
2 mH/10 mH
80 nF/300 nF
30 V DC
2)
10 mA
2)
0.3 W
2)
negligible
6 nF
Functional
values
galvanically isolated,
passive: 30 V DC / 250 mA
Open Collector
Full scale frequency
2 to 5000 Hz
galvanically isolated,
active: 0/4 to 20 mA
R
L
< 400
R
L
HART 250
1)
Permitted values in the event of simultaneous occurrence of concentrated inductances and capacitances.
2)
The interconnection must be assessed according to the valid construction provisions.
Transmitter
Terminal no. (inputs/outputs)
20 (+) 21 (–) 22 (+) 23 (–) 24 (+) 25 (–) 26 (+) 27 (–)
Assignment
Pulse/frequency output,
passive
Current output HART,
passive
Electric circuit Ex ia Ex ia
Safety-related
values
––U
i
I
i
P
i
L
i
C
i
30 V DC
500 mA
600 mW
negligible
6 nF
U
i
I
i
P
i
L
i
C
i
30 V DC
100 mA
1.25 W
negligible
6 nF
Functional
values
galvanically isolated,
passive: 30 V DC / 250 mA
Open Collector
Full scale frequency
2 to 5000 Hz
galvanically isolated,
passive: 4 to 20 mA
voltage drop 9 V
R
L
< [(V
p. supply
– 9 V) ÷ 25 mA]