Proline Promag L 400 Electrical connection
Endress+Hauser 27
Cable diameter
• Cable glands supplied:
– For standard cable: M20 × 1.5 with cable 6 to 12 mm (0.24 to 0.47 in)
– For reinforced cable: M20 × 1.5 with cable 9.5 to 16 mm (0.37 to 0.63 in)
• (Plug-in) spring terminals for wire cross-sections 0.5 to 2.5 mm
2
(20 to 14 AWG)
7.1.3 Terminal assignment
Transmitter
Supply voltage
Order code for "Power supply" Terminal numbers
1 (L+/L) 2 (L-/N)
Option L
(wide range power unit)
AC100 to 240 V
AC/DC24 V
Signal transmission 0-20 mA/4-20 mA HART with additional outputs and inputs
Order code for
"Output" and "Input"
Terminal numbers
Output 1 Output 2 Output 3 Input
26 (+) 27 (-) 24 (+) 25 (-) 22 (+) 23 (-) 20 (+) 21 (-)
Option H • 4-20 mA HART
(active)
• 0-20 mA
(active)
Pulse/frequency
output
(passive)
Switch output
(passive)
-
Option I • 4-20 mA HART
(active)
• 0-20 mA
(active)
Pulse/frequency/
switch output
(passive)
Pulse/frequency/
switch output
(passive)
Status input
PROFIBUS DP signal transmission
Order code for "Output" and "Input" Terminal numbers
Output 1
26 (RxD/TxD-P) 27 (RxD/TxD-N)
Option L B A
Order code for "Output":
Option L: PROFIBUS DP, for use in non-hazardous areas and Zone 2/div. 2
EtherNet/IP signal transmission
Order code for "Output" Connection via
Option N EtherNet/IP connector