System integration Proline Promag W 400
54 Endress+Hauser
EMPTY_MODULE module
This module is used to assign empty spaces arising from modules not being used in the slots
→  50.
9.2 Cyclic data processing EtherNet/IP
9.2.1 Cyclic data transmission
Cyclic data transmission when using the device master file (GSD).
Block model
The block model shows which input and output data the measuring device makes available for
implicit messaging. Cyclical data exchange is performed using an EtherNet/IP scanner, e.g. a
distributed control system etc.
Measuring device Control system
Transducer
Block
Input Assembly Fix
(Assem100) 44 Byte
→  56
Permanently assigned
input group
EtherNet/IP
Ouput Assembly Fix
(Assem102) 64 Byte
→  57
Permanently assigned
output group
Input Assembly Fix
(Assem101) 88 Byte
→  56
Configurable
input group
Input and output groups
Possible configurations
Configuration 1: Exclusive Owner Multicast
Input Assembly Fix Instance Size [byte] Min. RPI (ms)
Input Assembly Configurable Configuration 0 x 64 398
Output Assembly Fix O → T Configuration 0 x 66 64 5
Input Assembly Fix T → O Configuration 0 x 64 44 5
Configuration 2: Input Only Multicast
Input Assembly Fix Instance Size [byte] Min. RPI (ms)
Input Assembly Configurable Configuration 0 x 68 398
Output Assembly Fix O → T Configuration 0 x C7
Input Assembly Fix T → O Configuration 0 x 64 44 5