Proline Prosonic Flow B 200 Electrical connection
Endress+Hauser 21
Transmitter
+
1
2
4
+
3
2.1
2.2
2.3
4
+
1
2
+
3
1.1
1.2
1.3
1
2
A0018179
1 4-20 mA HART connection version with additional outputs, without integrated overvoltage protection
1.1 Output 1 (passive): 4-20 mA HART
1.2 Output 2 (passive): no assignment, pulse/frequency/switch output or 4-20 mA
1.3 Ground terminal for cable shield
2 4-20 mA HART connection version with additional outputs, with integrated overvoltage protection
2.1 Output 1 (passive): 4-20 mA HART
2.2 Output 2 (passive): no assignment, pulse/frequency/switch output or 4-20 mA
2.3 Ground terminal for cable shield
7.1.4 Requirements for the supply unit
Supply voltage
An external power supply is required for each output. The following supply voltage values
apply for the 4-20 mA and 4-20 mA HART current output:
Order code for
"Output"
Minimum
terminal voltage
Maximum
terminal voltage
Option A
1), 2)
: 4-20 mA HART
Option B
1), 2)
: 4-20 mA HART,
Pulse/frequency/switch output
For 4 mA: ≥ DC 16 V
For 20 mA: ≥ DC 12 V
DC 35 V
Option C
1), 2)
: 4-20 mA HART,
4-20 mA
For 4 mA: ≥ DC 16 V
For 20 mA: ≥ DC 12 V
DC 30 V
1) External supply voltage of the power supply unit with load (→  21)
2) For device versions with local display SD03: The terminal voltage must be increased by DC 2 V if backlighting is
used.
Load
Load for current output: 0 to 500 Ω, depending on the external supply voltage of the power
supply unit