Proline Prowirl R 200 Electrical connection
Endress+Hauser 29
21 3
+
-
+
-
+
-
4
5
5
78
6
6
6
6
6
6
.
-
A0019004
1 Controller (e.g. PLC)
2 Segment coupler PROFIBUS DP/PA
3 Cable shield
4 T-box
5 Measuring device
6 Local grounding
7 Bus terminator
8 Potential matching line
NOTICE
In systems without potential matching, the multiple grounding of the cable shield
causes mains frequency equalizing currents!
Damage to the bus cable shield.
Only ground the bus cable shield to either the local ground or the protective ground
at one end. Insulate the shield that is not connected.