Prosonic S FMU90 Flow Measurement PROFIBUS Mounting
Endress+Hauser 7
L00-FMU90xxx-17-00-00-xx-003
Wall mounting with mounting help (1)
2.2.2 Installation conditions of the DIN-rail housing
• The DIN-rail housing must be mounted outside hazardous areas in a cabinet.
• The housing is mounted on a DIN rail EN 60715 TH 35 x 7.5 or TH 37 x 15.
• Do not install the instrument in the vicinity of high-voltage lines, motor lines, contactors or
frequency converters. The installation regulations for high-voltage lines, motor lines,
contactors or frequency converters must be observed.
• To ensure easy mounting and opening of the housing, a distance of approx. 10 mm (0.39 in)
should be kept between the instruments.
• In order to avoid interference, do not route the sensor cables parallel to high-voltage or
electric power lines and not close to frequency converters.
Further information: Operating Instructions for Prosonic S FMU90, document number
BA00293F.
You will find this document in the Download Area of the Endress+Hauser Internet site.