Wiring Prosonic S FMU90 Flow Measurement PROFIBUS
18 Endress+Hauser
Additional elements on the terminal areas
Risk of electric shock!
Voltage at the terminals.
‣ Switch off the supply voltage before connecting the device.
‣ In a wet environment, do not open the cover if voltage is present.
3.4 Sensor connection
Information on the mounting of the sensors
3)
can be found in the following documents:
• Technical Information TI00189F (for FDU8x)
• Technical Information TI00396F (for FDU9x)
These documents are supplied with the sensors.
Designation Meaning/Remarks
Fuse Fuse: 2 A T /DC or 400 mA T/AC
Display Connection of the display or the remote display and operating module
Service Service interface for connection of a PC/Notebook via Commubox FXA291
Locking switch
Term. Bus termination (only applicable for instruments with PROFIBUS interface)
Address Bus address (only applicable for instruments with PROFIBUS interface)
• Basic information on the cyclic data exchange between the measuring instrument and
an automation system (e.g. PLC) are described in this document: Operating
Instructions "PROFIBUS DP/PA - Guidelines for planning and commissioning",
document number BA00034S.
• Further information: Operating Instructions for Prosonic S FMU90, document number
BA00293F.
3) The sensors FDU80/80F/81/81F/82/83/84/85/86/96 are not available anymore.