Prosonic S FMU90
10 Endress + Hauser
PROFIBUS DP interface
Auxiliary energy
Supply voltage/
Power consumption/
Current consumption
Galvanic isolation The following terminals are galvanically isolated from each other:
• auxiliary energy
•sensor inputs
• analogue output 1
• analogue output 2
• relay outputs
• bus connection (PROFIBUS DP)
Fuse •2 A T /DC
• 400 mA T /AC
accesible in the terminal compartment
Profile 3.0
Transmittable values • main value (level or flow, depending on the instrument version)
•distances
•counters
• temperatures
• average/difference/sum
• relay states
•rake control
• pump control
Function blocks • 10 Analog Input Blocks (AI)
• 10 Digital Input Blocks (DI)
• 10 Digital Output Blocks (DO)
Supported baud rates • 9.6 kbaud
• 19.2 kbaud
• 45,45 kbuad
• 93.75 kbaud
• 187.5 kbaud
• 500 kbaud
• 1.5 Mbaud
•3 Mbaud
•6 Mbaud
•12 Mbaud
Service Access Points (SAPs) 1
ID number 1540 (hex) 1540 (hex) = 5440 (dec)
GSD file EH3x1540.gsd
Addressing via dip switches at the instrument or via software (e.g. FieldCare)
Default address: 126 per software
Termination can be activated/deactivated in the instrument
Locking The device can be locked by hardware or software.
Instrument version Supply voltage Power consumption Current consumption
AC voltage
(FMU90 - ****A****)
90 ... 253 V
AC
(50/60 Hz) max. 23 VA max. 100 mA at 230 V
AC
DC voltage
(FMU90 - ****B****)
10,5 ... 32 V
DC
max. 14 W (typically 8 W) max. 580 mA at 24 V
DC