Prosonic S FMU90
8 Endress + Hauser
Input
Sensor inputs Depending on the instrument version, 1 or 2 of the sensors FDU91, FDU91F, FDU92, FDU93, FDU95 and
FDU96 can be connected. The Prosonic S identifies these sensors automatically.
In order to support existing installations, the sensors of the former series FDU8x can be connected as well. The
type of sensor must be entered manually.
#
Warning!
The sensors FDU83, FDU84, FDU85 and FDU86 with an ATEX, FM or CSA certificate are not certified for
connection to the transmitter FMU90.
External limit switches
(option)
Optionally, the Prosonic S FMU90 has four inputs for external limit switches (FMU90-********B***).
Switching options
external passive limit switch (NC/NO switch)
0: < 8 V; 1: > 16 V
Usage (examples)
pump feedback (for FMU90-*3******B***) and FMU90-*4******B***)
pump tariff control (for FMU90-*3******B***) and FMU90-*4******B***)
start/stop/reset of daily counters (for flow measurements)
(for FMU90-*2******B*** and FMU90-*4******B***)
min/max level detection, e.g. by Liquiphant
External temperature sensor Optionally, the Prosonic S FMU90 has an input for an external temperature sensor (FMU90-********B***).
Connectable sensors
Pt100 (3-wire or 4-wire connection)
A Pt100 with 2-wire connection may not be used due to its insufficient accuracy.
FMT131(from Endress+Hauser, see chapter "Accessories")
Usage (example)
Time-of-flight correction for a heated sensor (FDU91-***B*).
Sensor
FDU91
FDU91F
FDU92 FDU93 FDU95 FDU96
max. range
1)
in liquids
1) This table gives the maximum range. The range depends on the measuring conditions. For an estimation see
Technical Information TI 396F, chapter "Input".
10 m 20 m 25 m - -
max. range
1
in solids 5 m 10 m 15 m 45 m 70 m
Sensor
FDU80
FDU80F
FDU81
FDU81F
FDU82 FDU83 FDU84 FDU85 FDU86
max. range
1)
in liquids
1) This table gives the maximum range. The range depends on the measuring conditions. For an estimation see
Technical Information TI 189F, chapter "Planning Recommendations".
5 m 9 m 20 m 25 m - - -
max. range
1
in solids 2 m 5 m 10 m 15 m 25 m 45 m 70 m