Prosonic S FMU90
Endress + Hauser 15
#
Warning!
When using the public supply mains, an easily accesible power switch must be installed in the proximity of the
device. The power switch must be marked as a disconnector for the device (IEC/EN 61010)
!
Note!
In order to avoid interference signals, the sensor cables should not be laid parallel to high voltage or electric
power lines.
The cables may not be laid in the proximity to frequnecy converters.
Additional elements on the terminal areas
Terminals Pluggable spring-force terminals for connection of the cables are supplied in the terminal compartment. Rigid
conductors or flexible conductors with cable and sleeve can directly be inserted and are contacted
automatically.
1) In this case, terminals 9/10/11 are not present on terminal area A.
Designation Meaning/Remarks
Fuse Fuse: 2 A T /DC or 400 mA T/AC
Display Connection of the display or the remote display and operating module
Service Service interface for connection of a PC/Notebook via Commubox FXA291
Locking switch
Term. Bus termination (only applicable for instruments with PROFIBUS interface)
Address Bus address (only applicable for instruments with PROFIBUS interface)
Conductor cross section 0,2 mm
2
- 2,5 mm
2
Cable and sleeve cross section 0,25 mm
2
- 2,5 mm
2
min. stripping length 10 mm