Prosonic T Mounting
Endress+Hauser 7
2.3.2 Installation in narrow shafts
2.3.3 Installation conditions for flow measurements
• Install the device at the inflow side (B), as close above the maximum water level H
max
as
possible (take into account the blocking distance BD).
• Position the instrument in the middle of the channel or weir.
• Align the sensor membrane parallel to the water surface.
• Keep to the installation distance of the channel or weir.
Example: Khafagi-Venturi flume
L00-FMU30xxx-17-00-00-xx-003
A: Khafagi-Venturi flume; B: inflow; C: outflow; E: empty calibration; V: direction of flow
In narrow shafts with strong interfe-
rence echoes, we recommend using an
ultrasound guide pipe (e.g. PE or PVC
wastewater pipe) with a minimum dia-
meter of 100 mm (3.94 in).
Make sure that the pipe is not soiled by
accumulated dirt. If necessary, clean
the pipe at regular intervals.
L00-FMU30xxx-17-00-00-xx-010
A: venting hole
A
1xb
0
b
0
BD
A
E
BC
V
H
max