Prosonic T Mounting
Endress+Hauser 7
2.3.2 Installation in narrow shafts
2.3.3 Installation conditions for flow measurements
Install the device at the inflow side (B), as close above the maximum water level H
max
as
possible (take into account the blocking distance BD).
Position the instrument in the middle of the channel or weir.
Align the sensor membrane parallel to the water surface.
Keep to the installation distance of the channel or weir.
Example: Khafagi-Venturi flume
L00-FMU30xxx-17-00-00-xx-003
A: Khafagi-Venturi flume; B: inflow; C: outflow; E: empty calibration; V: direction of flow
In narrow shafts with strong interfe-
rence echoes, we recommend using an
ultrasound guide pipe (e.g. PE or PVC
wastewater pipe) with a minimum dia-
meter of 100 mm (3.94 in).
Make sure that the pipe is not soiled by
accumulated dirt. If necessary, clean
the pipe at regular intervals.
L00-FMU30xxx-17-00-00-xx-010
A: venting hole
A
1xb
0
b
0
BD
A
E
BC
V
H
max