RA33 Commissioning
Endress+Hauser 27
6.1 Quick commissioning/make it run
For quick commissioning of the "standard" batch controller application, you only have to enter
a few operating parameters in the menu Setup.
Prerequisites for quick commissioning:
RTD temperature sensor, 4-wire direct connection
Menu/setup
É Units: Select unit type (SI/US)
É Signal type: Select the signal type for flow (pulse or current)
É Unit: Select the flow unit
É Counter unit: Specify the unit for the volume counter
É Pulse value, value: Enter the unit and value for the pulse value of the flow transmitter (for
"pulse" signal type)
É Meas. range start and Meas. range end (for "current" signal type)
É Date/time: Set the date and time
The device is now operational and ready to control batching.
You can configure device functions, such as data logging, tariff function, bus connection and the
scaling of current inputs for flow or temperature, in the "Advanced setup" menu.
6.2 Device configuration
Detailed information on device configuration can be found in the operating instructions on the
CD-ROM which is delivered along with the device.