EasyManua.ls Logo

Endress+Hauser RA33 - Page 41

Endress+Hauser RA33
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Batch Controller RA33 Commissioning
Endress+Hauser 41
a0014191
Fig. 32: Display values in the Web browser
Just as in the display, you can switch between the display groups in the Web server. The measured
values are updated automatically (direct via "link": off/5s/15s/30s/60s). In addition to the mea-
sured values, status/limit value flags are also displayed.
The data can be read out via the Webserver in HTML or XML format.
When using an Internet browser, it suffices to enter the address http://<IP address> to display the
information as HTML in the browser. In addition, two versions of the XML format are available.
These versions can be integrated into additional systems as required. The two XML versions contain
all the measured values which are assigned to any group.
!
Note!
The decimal separator is always displayed as a period in the XML file. All times are given in UTC.
The time difference is indicated in minutes in the subsequent entry.
Version 1:
The XML file is available in ISO-8859-1 (Latin-1) encoding at the address http://<IP address>/
index.xml (alternatively: http://<IP address>/xml). However, this encoding cannot display some
special characters such as the sum sign. Strings such as digital status information are not transmitted.
Version 2:
A UTF-8 encoded XML file can be retrieved at the address http://<IP address>/main.xml All the
measured values and the special characters can be found in this file.
The structure of the channel values in the XML file is explained below:
<device id="ID0104" tag="Flow" type="INTRN">
<v1>12.38</v1>
<u1>m
3
/h</u1>
<vstslv1>2</vstslv1>
<hlsts1>ErS</hlsts1>
<vtime>20120105-004158</vtime>
<man>Endress+Hauser</man>
<param />
</device>
Day Description
tag Channel ident.
v1 Measured value of the channel as a decimal value
u1 Unit of the measured value.
vstslv1 Status of the measured value
0 = OK, 1 = warning, 2= error
hlsts1 Error description
OK, OC = cable open circuit, Inv: invalid, ErV: error value, OR: over range, UR: under
range, ErS: error sensor
vtime Date and time
man Manufacturer