Batch Controller RA33 Appendix
Endress+Hauser 61
11.1.3 Setup menu
In this setup, you can select only the most common/important operating options.
Special settings can also be configured via "Expert".
Units 100001-00 Select your unit system (SI or US units).
!
Note!
All units are switched to the selected unit system, but con-
figured values are not converted.
Signal type 210000-00 Pulse input for contact sensors as per EN 1434-2, Class ID
+ IE:
Pulse (current):
Current pulse input: = 8 mA low level, = 13 mA high
level.
Unit 210004-00 Specify the technical (physical) unit for the measuring
point connected to this input.
Counter unit 210005-00 Technical units of the count input, e.g. gal, cf , ... .
Pulse Value 210013-00 Unit for pulse value, e.g. pulse/l or l/pulse
Value 210003-00 Factor which, multiplied by an input impulse, yields the
physical value. Example: 1 pulse corresponds to 5 m
3
,
pulse value m
3
/pulse -> enter "5" here.
Decimal number, 8 digits including leading sign and deci-
mal separator.
Date/time Set date/time
Range start 210008-00 Transmitters convert the physical measured variable into
standardized signals.
Enter the beginning of the measuring range here.
Example: 0-100 m
3
/h of the sensor is transformed 4-20
mA: 0.
Meas. range end 210009-00 Enter the end of the measuring range here, e.g. "100" for a
transmitter with 0-100 m
3
/h.
Date/time Show and set date and time.
UTC time zone 120000-00 Current UTC time zone on (UTC = coordinated universal
time).
Actual date 120001-00 Actual date. Format as configured under date format.
Actual time 120002-00 Actual time. HH:MM, 12/24-hour as configured in the
time format.
Change Change the date and time here.
UTC time zone 120010-00
Date/time 120013-00
Advanced setup Additional settings that are not essential for the basic oper-
ation of the device.
System Basic settings that are needed to operate the device (e.g.
date, time, communication settings etc.)
Access code 100000-00
or
100010-00
(FieldCare)
4-digit number.
Using this code, you can protect the setup from unautho-
rized access. To change parameters, you first have to enter
the correct code. Factory setting: "0", i. e. changes are pos-
sible at any time.
Tip: write down the code and keep it in a place where it is
inaccessible to unauthorized persons.
Device tag 000031-00 Individual name of the device (max. 17 characters).
Decimal separator 100003-00 Select in which form the decimal separator character is to
be displayed