11.1.5 Expert menu
In the Expert menu, all parameters and settings of the device can be changed.
The menu contains all parameters / settings from the Setup menu in addition to those described
below.
Hardware Information on the hardware components.
Device running time 010050-00 Indicates how long the device was in operation.
Fault hours 010051-00 Indicates how long the device experienced a fault.
Ethernet Set-up required, if you are using the Ethernet interface of the
unit.
Only for devices with Ethernet interface.
Firmware Version 010026-00 Firmware version of Ethernet card. Please send these details
with any questions about the device.
Serial Number 010027-00 Serial number of Ethernet card. Please send these details with
any questions about the device.
Device options Hardware and software options of the device.
Optional outputs 990000-00
Communication 990001-00
Protocol 990007-00
Compensation 990009-00
Measured values Displays the current measured values of the device.
Hold 060000-00 Stops the entire measured value acquisition/storage.
Select "No" to exit the hold function.
!
Note!
The hold function is exited automatically after 5 minutes.
Outputs Current status of the outputs (if used).
Universal output 060120-00 Value currently output at the universal output.
Simulation Various functions/signals can be simulated for test purposes
here.
!
Note!
During simulation operation, normal measured value recording
is interrupted and the intervention is logged in the event log-
book.
Universal output 050200-00 Choose the value which should be output.
Select "Switched off" to exit the simulation.
!
Note!
The simulation is exited automatically after 5 minutes.
Open Collector 1/2 050205-00
050210-00
Select the frequency which should be output.
Select "Switched off" to exit the simulation.
!
Note!
The simulation is exited automatically after 5 minutes.
Relay 1/2 050215-00
050220-00
Manual activation of the selected relay.
!
Note!
The simulation is exited automatically after 5 minutes.
Direct Access Direct access to parameters (rapid access).
Service code 010002-00 Please enter service code to make service parameter visi-
ble.
!
Note!
For PC operating software only.