Wiring RIA15
22 Endress+Hauser
6.2 Connection in 4 to 20 mA mode
The following diagrams show how the process display unit is connected in 4 to 20 mA
mode.
Connection without backlighting Connection with backlighting
Connection with transmitter power supply
and transmitter
LED
-
+
-
-
+
+
I
Y
1
A0017704
1 Transmitter power supply
+
+
I
Y
1
-
-
LED
-
+
A0017705
1 Transmitter power supply
Connection with transmitter power supply
and transmitter using the auxiliary
terminal
-
-
+
+
I
Y
1
LED
-
+
A0017706
1 Transmitter power supply
+
+
I
Y
1
-
-
LED
-
+
A0017707
1 Transmitter power supply
Connection with PLC and transmitter
-
-
+
+
I
Y
1
LED
-
+
A0019720
1 PLC
-
-
+
+
I
Y
1
LED
-
+
A0019721
1 PLC
Connection without transmitter power
supply directly in the 4 to 20 mA circuit
+
2
-
I
Y
LED
-
+
A0017708
2 4 to 20 mA power source
+
2
-
I
Y
LED
-
+
A0017709
2 4 to 20 mA power source
6.3 Connection in HART mode
The following diagrams show how the process display unit is connected in HART mode.
6.3.1
HART
®
connection
NOTICE
Undefined behavior due to incorrect wiring of an actuator
When installing the process display unit together with an actuator, the Operating
Instructions for the actuator must be followed!
The HART
®
communication resistance of 230 Ω in the signal line is always necessary
in the case of a low-impedance power supply. It must be installed between the power
supply and the display unit.