Commissioning RIA15
40 Endress+Hauser
3. Set the desired parameters. For parameter descriptions, see the following table.
Setup -> Level (LEVEL) menu
The Level menu is only visible if the RIA15 has been ordered with the "FMR20 basic setting" option and
the display unit is operated in the HART mode (MODE = HART). The basic settings can be made at the
Micropilot FMR20 radar level sensor via the RIA15 using this menu.
Parameters Values visible at Description
Level MODE =
HART
This menu contains the parameters for configuring the
FMR20 level transmitter.
The Level menu and all the related submenus are only
visible if the RIA15 has been ordered with the "FMR20
basic configuration" option. The basic settings can be
made at the Micropilot FMR20 radar level sensor via the
RIA15 using this menu.
UNIT m
ft
Select the displayed unit
EMPTY Numerical value
0 to 100 m
Default 2 m
Empty calibration using keys -,+,E.
Enter distance from process connection to min. level
FULL Numerical value
–19 999 to 99 999
Full calibration using keys -,+,E.
Enter span from max. level to min. level
DIST Measured value Measured value (measured distance)
MAP
DI OK To be selected if the distance displayed matches the
actual distance. The device then records a mapping.
MAN To be selected if the range of mapping is to be defined
manually in the 'Mapping end point' parameter. A
comparison between the distance displayed and the
actual distance is not necessary in this case. Mapping
becomes active after approx. 20 s.
DI UN To be selected if the actual distance is unknown. No
mapping is recorded.
FACT To be selected if the present mapping curve (if one
exists) is to be deleted. The device returns to the "Confirm
distance" parameter and a new mapping can be recorded.