Recommended Cable Length, Size and Fuse Protection.
DC2DC Connection
Inputs
Require Length & Battery Cable Size
< 1.5 Meters
2)
2 Meters to 5
Meters
3)
Up to 10
Meters
3)
Greater than
10 Meters
3)
From Alternator Battery
10mm2 @ 12vdc
/ 6mm2 @ 24vdc
10mm2 @ 12vdc
/ 6mm2 @ 24vdc
16mm2 @ 12vdc
/ 8mm2 @ 24vdc
25mm2 @ 12vdc
/ 16mm2 @
24vdc
From Solar Panels
1)
4mm2 per solar
panel installed
4mm2 per solar
panel installed
4mm2 per solar
panel installed
4mm2 per solar
panel installed
Primary Battery
Connection
2)
10mm2 16mm2
Not
Recommended
Not
Recommended
Note: Cable size quoted is one way from battery to device, however suggested cable size is calculated with return run.
1)
Note: If solar panels are wired in Series (increased voltage), then typically 1 x 4mm2 cable run per series string
is suitable.
2)
Based on 3% voltage drop.
3)
Based on 10% voltage drop.
Recommended Fuse Protection
From Alternator Battery
50amp Maxi Fuse or Circuit Breaker no greater than 20cm from source
battery.
From Solar Panels
Fusing recommended no greater than 20cm from input to DC2DC
Charger. Typically 15amps per solar panel (consult your panel
specications for further details).
Primary Battery
Connection
40amp Maxi Fuse or Circuit Breaker.
Standard Temperature Sensor Connection
•
To install the temperature sensor, simply connect the RJ12 plug from the sensor to the
RJ12 Temperature Sensor Port located next to the Remote Port.
•
On the temperature sensor end, simply connect the ring terminals to the negative terminal
of the main house battery bank.
Optional Remote Display Connection
To install the optional Remote Display in a specic location, a 6 pin standard RJ12 cable
(maximum length 7.5 meters) is required.
• Install the standard RJ12 cable in your desired location.
• Connect one end of the RJ12 cable to the Remote Port and the other end of the cable to
the Display Panel. Please note polarity.
• The Remote Display is now ready for use.