E08
CH1 Output Short Circuit
This means there is a Short Circuit on the DC output to your Main/House battery.
If this is displayed, check the following:
The output wires are not shorted together.
The output wires are wired correctly and not reverse polarity.
A01
Over Temperature Warning
When the charger’s internal temperature is > 60°C, the unit will shut down to protect itself. The unit will return back to
normal charging once the internal temperature is < 58°C
Check to make sure the fan is working.
Make sure the unit has good ventilation.
A02
BTS High Temperature Warning
When the battery temperature sensor is > 58°C, the unit will shut down to protect the batteries. The unit will return
back to normal charging once the battery temperature sensor is < 56°C.
Check to make sure the batteries are not hot.
Make sure the batteries have good ventilation.