EasyManuals Logo

ENERGY KINETICS System 2000 Installation & Service Manual

ENERGY KINETICS System 2000
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
Frontier Gas Heat – PN 10-2027 – January 2016 34
Annual Tune Up & Inspection
Step 10 Start Burner & Check Safety Functions.
Check & Record: Air box cover must be in place before testing.
Refer to burner manual for recommended settings.
1. Check manifold pressure with the burner running by installing a hose barb fitting
in the combination gas valve outlet pressure tap. Adjust valve regulator if
necessary so the reading is 3.5”w.c. for either LPG or natural gas.
2. Draft Loss: A difference of 0.04” or less between flue box (1) and “over fire” test
port (2).
Sidewall Vent: Draft over fire of -0.10” to -0.12”wc after 15 minutes of continuous
burner operation.
Chimney: Draft over fire should be -0.02” to -0.12”w.c.).
3. Check CO
2
/O
2
at over fire test port (2) Natural: CO
2
:8.6%-9.2%, O
2
5.5%-4.5%
LPG: CO
2
:9.7%-10.7%, O
2
6.0%-4.5%
4. Stack Temp: 350º-450º F. (at stack or flue box port)
5. Check CO: 400 ppm Max Air-free (Refer to installation manual for Air-free
method of measuring CO).
6. Verify DualGard set to 205º/215º F.
7. Test Safety High Limit operation:
a. Remove all heat and hot water calls (No input lights on left side of manager).
b. Turn System switch off, then remove red sensor lead from the left side quick
connect.
c. Restore power. The E100 code will flash on the manager’s display, and the
burner should start momentarily.
d. At approximately 205
o
F to 215
o
F, the high limit aquastat should shut off
burner.
8. Verify flame failure lockout of Carlin 60200FR burner control
a. Connect hose from manometer to hose barb fitting in the combination gas
valve outlet pressure tap.
b. Close the main manual gas valve and turn the combination gas valve knob to
ON.
c. Turn on power to System 2000 boiler and adjust a thermostat to call for heat.
d. Burner motor will start. The burner control will run for 30 seconds (pre-purge),
then start the ignitor. Approximately one second later, the combination gas
valve will open. (The manometer should show almost no pressure, because
the main manual gas valve is closed.)
e. After 4 seconds, the burner control will lockout and turn on the red LED. The
ignitor will shut off and the gas valve will close. Turn off power and adjust the
thermostat to stop the call for heat.
If lockout does not occur, replace the burner control.
9. Sidewall Vent Only:
a. Remove power from the inducer. (option switch 2 on a Digital Manager)
b. Start burner. Safety lock-out should occur in approximately 1 minute.
c. Restore power to the inducer.
Step 8 Check Zone Valves
Open/Close zone valves several times to see that they move freely.
Step 9 Backflush Plate Heat Exchanger
1. Close the valve underneath the domestic hot water circulator.
2. Open drain valve above the circulator to back flush the heat exchanger.
3. If domestic water supply is “hard” (lime), consider installing Scale Stopper (Item
no. 10-0650).
4. Set temperature feeding hot water tank (above heat exchanger) by adjusting the
ball valve below the bronze circulator. Adjust the ball valve with the burner running
and a continuous flow of hot water from a fixture. You should just be able to hold
your hand on the pipe.
Step 7 Close Front Cover
1. Install (3) upper nuts and washers.
2. Tighten nuts (5) uniformly.
3. Check and tighten (6) rear cover nuts.
4. Check Flue Pipe.
5. Check chimney base and clean if necessary
Digital
Manomete
r
1
2
3
4 5
1
2
Safety High
Limit

Other manuals for ENERGY KINETICS System 2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ENERGY KINETICS System 2000 and is the answer not in the manual?

ENERGY KINETICS System 2000 Specifications

General IconGeneral
BrandENERGY KINETICS
ModelSystem 2000
CategoryBoiler
LanguageEnglish

Related product manuals