EasyManua.ls Logo

EnerSys alpha Matrix C16 - Ground Installation; Ground Termination Summary; Connecting Ground Lug

EnerSys alpha Matrix C16
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
C048-725-30 Rev. B (01/2020)
4.3 4.3 Ground InstallationGround Installation
DO NOT ENERGIZE THE PANEL BEFORE CHASSIS
GROUND IS CONNECTED�
CAUTION!
The chassis ground is located on each side of the panel� A two
hole lug landing position is provided per side� See table below
for termination information. A minimum of #6 AWG chassis 
ground cable is required�
IMPORTANT: Grounding hardware not included� A properly-
sized grounding conductor must be installed per NEC
(250�122)
Table 2. Ground Termination Summary
TWO HOLE
LANDING
TYPE
HOLE/
STUD SIZE
CENTER
TO
CENTER
RECOMMENDED
TORQUE VALUE
Threaded Insert 1/4in-20 5/8in 90in-lbs
Step 1. Connect the lug to the chassis (see Figure 8) with the
included 1/4in-20 hardware� Make sure heat shrink and
no-oxide compound are applied appropriately prior to
attachment�
Step 2. Torque the fasteners to 90in-lbs�
Figure 8. Chassis Ground Connection

Table of Contents