4.7 4.7 Alarm InstallationAlarm Installation
The Matrix C16 has Form-C dry alarm contacts for remote
alarm monitoring� An 8p8c- (RJ-45) modular jack can be
found in the center of the panel when viewed from the rear� It
is the lower of the two jacks as shown in Figure 14� Plug a Cat
5/5e/6 UTP cable with a TIA/EIA T568B termination into the
alarm jack� Refer to Table 4 below for termination pinout�
Table 4. Alarm Contact PinOut
PIN 1 PIN 2 PIN 3 PINS 4-8
COM NC NO Reserved
4.8 4.8 Breaker InstallationBreaker Installation
SLIMLINE BREAKERS RATED GREATER THAN
65A DO NOT CARRY A UL 489 RATING AT THIS
TIME�
NOTICE:
MAKE SURE CIRCUIT BREAKERS ARE IN THE
OFF POSITION PRIOR TO INSTALLATION�
ENSURE CIRCUIT BREAKERS ARE COMPLETELY
INSERTED�
CAUTION!
There are 16 breaker positions in the Matrix C16 breaker panel�
Step 1. Remove the breaker compartment door from the panel
by loosening the two thumb screws on the door�
Step 2. Select a breaker of sucient ampacity and insert it into
the desired output circuit, making sure to seat the
breaker securely (see Figure 15)�
NOTE: A breaker legend is applied to the inside of the
compartment door to allow an installer to mark the use of each
breaker�
Step 3. Once all desired circuit breakers have been installed,
reinstall the breaker compartment door and secure it
with the thumb screws�
Figure 14. Alarm Jack
Figure 15. Breaker Installation