4.7 4.7 Alarm InstallationAlarm Installation
The Matrix C16 has Form-C dry alarm contacts for remote
alarm monitoring� An 8p8c- (RJ-45) modular jack can be
found in the center of the panel when viewed from the rear� It
is the lower of the two jacks as shown in Figure 14� Plug a Cat
5/5e/6 UTP cable with a TIA/EIA T568B termination into the
alarm jack� Refer to Table 4 below for termination pinout
Table 4. Alarm Contact PinOut
PIN 1 PIN 2 PIN 3 PINS 4-8
COM NC NO Reserved
4.8 4.8 Breaker InstallationBreaker Installation
SLIMLINE BREAKERS RATED GREATER THAN
65A DO NOT CARRY A UL 489 RATING AT THIS
TIME
NOTICE:
MAKE SURE CIRCUIT BREAKERS ARE IN THE
OFF POSITION PRIOR TO INSTALLATION�
ENSURE CIRCUIT BREAKERS ARE COMPLETELY
INSERTED
CAUTION!
There are 16 breaker positions in the Matrix C16 breaker panel�
Step 1. Remove the breaker compartment door from the panel
by loosening the two thumb screws on the door
Step 2. Select a breaker of su󰀩cient ampacity and insert it into 
the desired output circuit, making sure to seat the
breaker securely (see Figure 15)�
NOTE: A breaker legend is applied to the inside of the
compartment door to allow an installer to mark the use of each
breaker
Step 3. Once all desired circuit breakers have been installed,
reinstall the breaker compartment door and secure it
with the thumb screws�
Figure 14. Alarm Jack
Figure 15. Breaker Installation