FUNCTION parameters
Parameter Description Range
6D Extended hold open time function. Off (00) / On (01) 00÷01
67 Door type. Single sliding (00) / Biparting (01) 00÷01
90
(DAS902MP)
Function select terminal 3. No function (00) / Nurse function (01) / Interlock
out (03)
00÷03
91
(DAS902MP)
Function select terminal 4. No function (00) / Open/Close function (01) / Interlock
disable (02) / inner impulse 2 monitoring (03) / Interlock in (04)
00÷04
93
(DAS902MP)
Function select terminal 2. No function (00) / Close function (01) / Inner impulse
2 (03)
00÷03
99
(DAS902MP)
Function select terminal 6. No function(00) / Sustainable Disable (01)/
Selector Disable (02).
00÷02
POSITION parameters
Parameter Description Range
11
Partial open position
00-99%
57
Low speed distance, opening
00-99cm
58
Low speed distance, closing
00-99cm
DRIVE parameters
Parameter Description Range
15 Run program. Smooth (01) to max performance (05) 01÷05
49 Opening max force 02÷23N x10
4A End checking closing thrust 00÷23N x10
50 Closing max force 02÷23N x10
64 Power supply type.150W (01) / 75W (02) 00÷02
68 Door weight 00÷40kg x10
69 Friction 00÷99N
70 Motor type. DAS200 (15) / DAS200HD-RF (16) / DAS200RG (17) 15÷17
71 Max motor power 03÷15W x10
EMERGENCY parameters
Parameter Description Range
10
Emergency unit monitoring. Off (00) / Convenience monitoring (01) / Redundant
monitoring (02)
00÷02
36 Emergency action. Closing (00) / opening (01) 00÷01
37 Emergency Action in OFF Mode. Off (00) / On (01) 00÷01
38 Convenience battery. Off (00) / On (01) 00÷01
40 Emergency unit test interval 04÷23hours
41 Battery type. No battery (00) / 12V (01) / 24V (02) 00÷02
94
(DAS902MP)
Fire impulse function terminal 18/19. Off (00) / On (01) 00÷01
95
(DAS902MP)
Emergency open impulse function 5. Off (00) / On (01) 00÷01
96
(DAS902MP)
Emergency button configuration 5. N.O. (00) / N.C. (01) 00÷01