43
IP2266EN
EN
Extended Hold Open Time Function (00÷01)
+ 5s hold open time on doors often reopening during closing.
00= Off.
01= On.
Control unit electronic mode selector group (01÷10)
FUTURE USE
MOTOR CONTROL PARAMETERS
Parameter Description
Factory
setting
Installation
setting
Motor Type (15÷17)
15= DAS200
16= DAS200HD / DAS200RF
17= DAS200RG
FACTORY SET
Max Motor Power (03÷15)
The max amount of power the motor can be supplied with.
DAS902MP PLUS MODULE PARAMETERS
Parameter Description
Factory
setting
Installation
setting
Function Select terminal 3 - DAS902MP (00÷03)
00= NO FUNCTION.
01=
Nurse function. The door will open to partial opening in
operation mode selections EXIT, AUTO and AUTO PARTIAL.
02= DO NOT USE.
03= Interlock out. When configuring for interlock also set
parameter 6A = 01.
Function Select terminal 4 - DAS902MP (00÷04)
00= NO FUNCTION.
01= Open/Close Function . One impulse opens the door the
next impulse closes the door. Available in operation
mode selections EXIT, AUTO, PARTIAL.
02= Interlock disable function. Disables interlock, both doors
can be open at the same time.
03= Inner impulse 2 monitoring. Sets inner impulse 2 mo-
nitoring for the second inner impulse on the DAS902MP
unit. Set also parameter 93 = 03.
04= Interlock in. When configuring for interlock also set
parameter 6A = 01.
Open/Close Timeout, terminal 4 - DAS902MP (00÷60
minutes)
The time set in this parameter controls when a door shall
start closing automatically if left open by an Open/Close
impulse.
00 min= no automatic closing.