MAGDUO Control Panel Engineering and Commissioning Manual
47
3. TECHNICAL EVENT Operation of I/P 1 will signal a
technical event at the control panel.
Panel outputs will be triggered but the
control panel will read technical alarm
and no fire indication will be given.
4. DISABLEMENTS Operation of I/P 1 will activate a
disablement on the control panel.
5. DAY-NIGHT MODE Operation of I/P 1 will activate the day
mode on the control panel (MAGDUO
FlexiPoint devices will be disabled;
Devices will be disabled for smoke
only but not for heat).
6. PROGRAM I/P 1 OFF I/P 1 will not be active.
This active control will allow the engineer to view or change the
operation of the control event set for programmable input 1. Use the
UP and DOWN arrow keys to toggle through the following options. To
confirm the changes press ENTER.
1. SILENCE ALARMS Operation of I/P 1 will silence the
alarms.
2. RESET SYSTEM Operation of I/P 1 will reset the panel.
3. SOUND ALARMS Operation of I/P 1 will send the
evacuate signal to the panel.
4. SILENCE BUZZER Operation of I/P 1 will silence the
control panel buzzer.
This active control will allow the engineer to view or change the
operation of the remote fire event set for programmable input 1. Use
the UP and DOWN arrow keys to toggle through the following options.
To confirm the changes press ENTER.
1. REMOTE FIRE FULL Operation of I/P 1 will signal a
remote fire at the control
panel. All sounders and relays
will operate.
2. REMOTE FIRE NO RELAYS Operation of I/P 1 will signal a
remote fire at the control
panel and only the sounders
will operate.
This active control will allow the engineer to view or change the
operation of the technical event set for programmable input 1. Use the
10. Panel I/O
1. Programmable I/P 1
1. Input Type
1. Control Event
01/09/09 20:13 ENGR
1.SILENCE ALARMS
2.RESET SYSTEM
Press Enter Key
10. Panel I/O
1. Programmable I/P 1
1. Input Type
2. Remote Fire Event
01/09/09 20:13 ENGR
1.REMOTE FIRE- FULL
2.REM FIRE,NO RELAYS
Press Enter Key
10. Panel I/O
1. Programmable I/P 1
1. Input Type
3. Technical Event
01/09/09 20:13 ENGR
TECHNICAL EVENT
1.LATCH 2.NON-LATCH
Press Enter Key