7.2.3 CLEANING THE COIL
Every year, verify that the fin pack is not clogged from dust or anything else that does not allow
the normal air flow; if necessary, use a jet of compressed air to clean the heat exchanger. To
prevent damage to the fins or the pipes on the heat exchanger, never use steel tools or sharp
objects to clean the spaces between the fins.
7.3 TROUBLESHOOTING
Here is a list of possible problems and malfunctions, their causes and the procedures that
you or the technician service must perform to correct the malfunction.
In case of other problems, contact the area distributor or EURAPO service department.
PROBLEM POSSIBLE CAUSE SOLUTION
The unit does not deliver air Lack on the power supply Verify the network voltage and/or the
integrity of the fuse on the electronic
card of the control and the rightness of
the electrical connections
Set - Point reached Check the control setting
In presence of WS (minimum water
temperature thermostat), hot water
temperature < 35°C, insufficient wa
-
ter flow and/or temperature in coil, or
damaged water sensor (WS)
Check the water temperature and wa-
ter flow on the coil and/or the correct
working of the water sensor (WS)
Electric motor burnt Replace the component
The fancoil issues an anomalous
noise
The filter and/or the coil is clogged Clean the filter and/or the coil
Vibrations caused by a wrong installa
-
tion and/or loose fixing screws
Verify carefully and carry out the
corrective actions
Unbalanced fan deck Replace it
Insufficient water and/or air volume The filter and/or the coil is clogged Clean the filter and/or the coil
The fan speed is too low Change the position of the speed
selector
The air delivered by the unit is not hot
or cold enough
Water and/or air temperature at the
entry of the fancoil does not comply
with the expected values
Verify the available power and the in
-
stalled power.
Operate accordingly
The pump is not powerful enough to
handle operational requirements
Replace the pump with a pump suit
-
able to the installation requirements
In case of other problems, contact the area distributor or EURAPO service department.
In case of fire, in order to prevent risk of electrocution, do not use water.