VFL Series User Manual v2.0 10/20
Same as ‘A1FU’ for Alarm 2.
See Alarm
function section
Select a specialty mode from the
Alarm mode list (Section 11.3).
RS-485
controller
address
Set a controller address for
optional RS-485 communications.
The setting must be ‘0’ when the
option is not installed.
Communication speed for RS-485
interface. See the RS-485 Interface
paragraph below for more.
11.1 Input Type Selection
Set the ‘TYPE’ parameter in Menu 4, above. See the available settings in the table below. The
selection must match the controller’s hardware configuration. Contact Extech if unsure. See
the Specifications section for the range and resolution data for each type.
Input Type Selections for the ‘TYPE’ parameter
The controller hardware is configured
at the factory per the part number
used when ordering (check the meter
label if unsure).
Converting from one input type to
another may require a hardware
modification.
Linear mode (voltage or current input)
11.2 Low and High Limit Considerations
The Low and High Limit settings (Menu 4, Options) default to the low and high range values of
the controller’s input type (see the Specifications for the input types and their ranges).
The High/Low Limit ‘span’ is directly proportional to the size of the Proportional Band, as the
Proportional band value (‘Pb’) is set as a percentage of span (Menu 3, PID). The wider the
span, the wider the Proportional Band.
The span also sets the low and high boundaries for basic operation. For example, the setpoint
cannot be adjusted higher than the high limit or lower than the low limit settings.