Winter Mode
The stove operates controlling both thermostats: the stove shuts down, after a delay of 15
minutes, only when the temperatures set on both thermostats have been reached.
Status of inputs ING1 and ING2:
• Closed contact to be satisfied
• Open contact satisfied (t1 and t2 on display D2 flashing)
Winter Mode
Status of terminals Status of outputs Stove status
ING1 connected external contact
ING1 closed and ING2 closed
ING2 connected external contact
OUT4 active (230 V, 50 Hz)
OUT3 deactivated (0 V)
Stove on
ING1 open and ING2 closed
OUT4 deactivated (0 V)
OUT3 active (230 V, 50 Hz)
Stove on
ING1 closed and ING2 open
OUT4 active (230 V, 50 Hz)
OUT3 deactivated (0 V)
Stove on
ING1 open and ING2 open
OUT4 deactivated (0 V)
OUT3 active (230 V, 50 Hz)
Stove off
Summer Mode
The stove operates controlling the status of the priority input (ING1): when the thermostat is
satisfied, the stove shuts down immediately.
Status of input ING1: Closed contact to be satisfied
Open contact satisfied (t1 on display D2 flashing)
Status of input ING2: ignored
Summer Mode
Status of terminals Status of outputs Stove status
ING1 connected external contact
ING1 closed and ING2 closed
ING2 connected external contact
OUT4 active (230 V, 50 Hz)
OUT3 deactivated (0 V)
Stove on
ING1 open and ING2 closed
OUT4 deactivated (0 V)
OUT3 active (230 V, 50 Hz)
Stove off
ING1 closed and ING2 open
OUT4 active (230 V, 50 Hz)
OUT3 deactivated (0 V)
Stove on
ING1 open and ING2 open
OUT4 deactivated (0 V)
OUT3 active (230 V, 50 Hz)
Stove off